UGOLINI 'HT'
/SANISERV/ TAYLOR GRANITA MACHINE
Preventive
Maintenance
Weekly maintenance of ‘HT’
model
1- the
machine is air-cooled. Allow 3 to 4" of space
around it for free airflow.
2- keep
the condenser coil (radiator)
clean to allow full ventilation. The compressor must be kept cool for
efficient working and long life.
3- do not back the machine to the wall as it reduces
the air circulation.
4- do not place a heat generating equipment (coffee brewer,
espresso machine etc.) close
to the left side of the machine. The condenser fan will draw warm air in and slow
the cooling of
machine.
5- use a dedicated 115 V, 15 Amp electric outlet for a
2-bowl and 115V 20 Amp. outlet for a 3-bowl unit. Using a long cord or extension cord will drop
the voltage. Machine will not operate or freeze
as well, when the voltage supply drops to 108 or
lower.
6- for better visibility, keep the bowls
full with product. Do not
allow the
level of product in the bowl drop below the level of
spiral blade. The product
will over freeze and increase load
on the augers & gearmotors.
7-
adjust viscosity when you change the product
or as necessary
or
8- do not leave the
machine in
"freeze mode" overnight.
9-
prevent leakage inside the machine. To do so follow the step
below:
Ø
clean old
lube & lubricate gear shaft every three
months
Ø
replace
gear shaft
o-rings (item # 38 on diagram)
Ø replace rear seal (part # 10) every 12
weeks.
Ø
replace front bushing (part # 37 'ht' diagram)
every 6 months.
Ø
during
cleaning of the machine, check the following parts for
signs
of wear:
1- the
outer spiral blade (diagram part # 13) - the nipple shaped
front tip of the outer spiral should be
evenly rounded. Replace it if the tip is slanted on one side
(average life 8 months).
2- check the thrust
washer (diagram # 8).
Replace it if a pimple is formed in the
center.
3- check the five auger parts
(diagram # 12)
(auger parts chip at the point where they lock into each other. Chipped piece
overrides the piece
in front & pushes the bowl forward. This will
cause visible back &
forth movement on the serving handle (like a breathing
chest). Replace the chipped auger
part.
Note: product
freezes faster or over freezes inside the bowl
when
1-
Brix
is below 12 (sugar content is below 17%) or
2-
the auger stops turning or is turning slow to scrape
the frozen product. (Auger
turns 38 circles in a minute). Check the reason why auger
has slowed down or stopped
turning
3-
the micro switch is stuck in ‘on’ position
or
4-
the solenoid valve is
faulty. |